What Is a Safety Integrity Level (SIL)?

What Is a Safety Integrity Level (SIL)?

How SIL levels are defined in IEC 61508 and IEC 61511, how the required SIL is decided and what it takes to achieve it

A Safety Integrity Level (SIL) is a measure of how much risk reduction a safety instrumented function must provide. It is defined in the international functional safety standards IEC 61508 and, for the process industries, IEC 61511. The higher the SIL, the more reliable the safety function has to be. In process plants, a SIL is assigned to each safety instrumented function, such as an automatic shutdown on high pressure, based on how dangerous the hazard is.

What are the SIL levels?

There are four levels. For functions that are called on rarely (low demand mode, typical in process plants), each level corresponds to a range of average probability of failure on demand (PFDavg) and a risk reduction factor (RRF):

SILPFDavgRisk reduction factor
SIL 10.1 to 0.0110 to 100
SIL 20.01 to 0.001100 to 1,000
SIL 30.001 to 0.00011,000 to 10,000
SIL 4below 0.0001above 10,000

In practice, most process industry functions are SIL 1 to SIL 3. SIL 4 is very rare, and a requirement that high usually prompts a redesign of the process to remove the hazard instead.

How is the required SIL decided?

SIL determination is part of the hazard and risk assessment. The team estimates the risk of a hazardous event without the safety function and compares it with the risk the organisation can tolerate. The gap is the risk reduction the function must provide, which sets its SIL. Common methods include layer of protection analysis (LOPA) and risk graphs.

Is achieving a SIL just a calculation?

No. Meeting a target SIL involves more than reaching the right PFDavg. The design must also meet requirements on hardware fault tolerance and on the systematic capability of the devices and software used, and the function must be proof-tested at the intervals assumed in the calculation. IEC 61511 also sets out a full safety lifecycle, from specification and design through operation, maintenance and modification, along with the competence of the people involved.

Who needs to understand SIL?

  • instrumentation and control engineers who design safety instrumented systems
  • process safety engineers who lead hazard studies and LOPA
  • operations and maintenance teams who run, test and bypass safety functions
  • managers responsible for functional safety management and compliance

What makes up a safety instrumented function?

Every safety instrumented function has three parts. Sensors detect the hazardous condition, for example pressure transmitters on a vessel. A logic solver, the safety instrumented system controller, decides when to act. Final elements carry out the action, such as a shutdown valve that closes or a pump that stops. The SIL applies to the whole function, so a reliable logic solver cannot make up for a single, poorly maintained valve. Designers often use redundancy, such as two-out-of-three voting on transmitters, to reach the required reliability and reduce spurious trips.

A worked example of SIL determination

Imagine a vessel that could be overpressured if a control loop fails. The team estimates that the loop fails about 0.2 times a year. A relief valve reduces the risk, with an assumed probability of failure of 0.01, and an operator alarm with time to respond adds a further factor of 0.1. Together, these give a frequency of 0.2 × 0.01 × 0.1 = 0.0002 events a year. If the company's tolerable frequency for this consequence is 0.00001 a year, the safety function must reduce the risk by a further factor of 20. That requires a PFDavg of 0.05 or better, which falls in the SIL 1 range.

Real assessments use agreed company data and criteria, and each protection layer must be independent and auditable before it can be counted.

How are proof tests and bypasses managed?

Many failures in safety instrumented systems are hidden: a valve may be stuck open without anyone knowing. Proof tests are designed to reveal these failures, and they must be done at the interval assumed in the SIL calculation. Bypasses, used during maintenance or start-up, remove protection, so they need authorisation, time limits and compensating measures. Poorly controlled bypasses are a common finding after incidents.

What changed in IEC 61511 Edition 2?

The second edition of IEC 61511, published in 2016, strengthened several areas. It added a requirement to carry out a security risk assessment of the safety instrumented system, recognising cyber threats. It also placed more emphasis on the competence of people working on the system and on managing the full safety lifecycle.

Where to start

Coventry Academy's Functional Safety Leadership and Compliance Management course covers IEC 61508 and IEC 61511 for engineers and managers. For related subjects, browse our instrumentation and process control training courses. Coventry Academy is certified to ISO 9001:2015 and ISO 29993:2017.

Sources